Description
Edwards SD-TRK Remote Test Station, 2 WattCondition: * New surplus stock, in OEM packaging. As pictured. Additional Notes: * Compatible electrical boxes North American 1-gang box Standard 4-in square box, 1-1/2 inches deep, with 1-gang cover * LED indicators: Alarm (red) * LED type: Clear lens * Wire size: 12 to 22 AWG * Resistance per wire: 10 , max. * Current requirements: Included in controller specification * LED circuit ratings Voltage: 3 Vdc, max. Current: 30 mA, max. * Switch ratings (SD-TRK) Voltage: 125 Vdc, max. Current: 4 A, max. * Switch ratings (SD-TRM) Voltage: 200 Vdc, max. Current: 0.5 A, max. * Compatible detectors: SuperDuct conventional two-wire and Signature duct smoke detectors Operating environment Temperature: 0 to 55 C (32 to 131 F) Humidity: 93% RH, noncondensing Storage temperature: -20 to 60 C (-4 to 140 F) Edwards SignalingSD-TRK

Reviews